BECKHOFF BK3000 User Manual

Page 60

Advertising
background image

Appendix

60

BK3xxx/LC3100

The FMS objects for various terminals appear as follows:

KL3002, KL3012,
KL3022, KL3032,
KL3042, KL3052,
KL3062, KL3202,
KL3302,
KL2502, KL4002,
KL4012, KL4022,
KL4032

Object index i (channel 1), i+2 (channel 2)
Data type

Record of Unsigned8, Unsigned16

Data length

3

Access rights Read/Write

Object index i+1 (channel 1), i+3 (channel 2)
Data type

Record of Unsigned8, Unsigned16

Data length

3

Access rights Read

KL3004, KL3014,
KL3024, KL3034,
KL3064,
KL4004, KL4014,
KL4024, KL4034

Object index i (channel 1), i+2 (channel 2), i+4 (channel 3), i+6 (channel 4)
Data type

Record of Unsigned8, Unsigned16

Data length

3

Access rights Read/Write

Object index i+1 (channel 1), i+3 (channel 2), i+5 (channel 3), i+7 (channel 4)
Data type

Record of Unsigned8, Unsigned16

Data length

3

Access rights Read

KL1501, KL5001

Object index i
Data type

Record of Unsigned8, Unsigned32

Data length

5

Access rights Read/Write

Object index i+1
Data type

Record of Unsigned8, Unsigned32

Data length

5

Access rights Read

KL5101

Object index i
Data type

Record of Unsigned8, Unsigned16, Unsigned8, Unsigned16

Data length

6

Access rights Read/Write

Object index i+1
Data type

Record of Unsigned8, Unsigned16, Unsigned8, Unsigned16

Data length

6

Access rights Read

KL6001, KL6011,
KL6021

Object index i
Data type

Octet string 6

Data length

6

Access rights Read/Write

Object index i+1
Data type

Octet string 6

Data length

6

Access rights Read

Programmed configuration

The configuration tool allows further objects to be defined, into which any
desired process data can be collected. The index range above 1000 is
available for this. The bus coupler software needs the configuration tool to
supply it with the offset and the length in the process image, and must
know whether input or output data are involved. The first programmed FMS
object is allocated index 1000, after which the index increases without
gaps. If the programmed configuration is selected, the objects described
above in association with auto-configuration are omitted. The newly
generated FMS objects have the following properties:

Object index

1000 + x

Data type

Octet string

Data length

Sum of the data widths of the associated terminals (byte align)

Access rights

read only (for input data)
read write (for output data)

Advertising