PROFIBUS coupler BK3xx0 in the PROFIBUS DP

24

BK3xxx/LC3100

PROFIBUS coupler BK3xx0 in the PROFIBUS DP


Introducing the system

The PROFIBUS enjoys a very wide acceptance in automation technology
due to its openness and its wide manufacturer-independent distribution.
The PROFIBUS was developed in the course of a group project on the
fieldbus concept which aimed at agreeing on a standard. Numerous
different products are now available from independent manufacturers
which all conform to the standard DIN 19245 parts 1 and 2. Standards-
conform PROFIBUS devices can be operated on any bus system.

PROFIBUS specifies the technical and functional characteristics of a serial
fieldbus system which can be used to network distributed digital and
analog field automation devices with low range (sensor/actuator level) to
midrange performance (cell level). PROFIBUS makes a distinction
between master and slave devices; master devices are those which govern
the data traffic on the bus.

A master may send messages without an external request, provided it has
the authority to access the bus. The PROFIBUS protocol also describes
masters as "active subscribers”.

Slave devices are peripheral devices. Typical slave devices are sensors,
actors, signal transformers and the Beckhoff bus couplers BK3000,
BK3100, BK3110 and BK3010. They are not given authority to access the
bus, so they may only acknowledge the messages they receive, or pass
messages to a master when requested to do so. Slaves are also described
as "passive subscribers”. Beckhoff bus couplers are passive subscribers
which support PROFIBUS DP and PROFIBUS FMS. They are also
described as "FMS/DP combislaves”.

PROFIBUS DP

PROFIBUS DP is designed for rapid data exchange at sensor/actor level,
where centralized control devices (such as stored program control units)
communicate with decentralized input and output devices by means of a
fast serial connection. The exchange of data with these decentralized
devices is carried out predominantly cyclically. The centralized control unit
(master) reads the input data from the slaves and writes the output data to
the slaves, whereby the cycle time of the bus needs to be shorter than the
program cycle time of the central control unit, which will be under 10 ms in
many applications.

Rapid data throughput alone is not sufficient for the successful
implementation of bus system. Ease of handling, good diagnostic facilities
and fault-proof data transfer technology must all be provided in order to
fulfill the users’ requirements. The characteristics have been optimally
combined in PROFIBUS DP.

At a transfer rate of 1.5 Mbit/s (BK3000 and BK3010) PROFIBUS DP will
take 6 ms to transfer 512 bits of input data and 512 bits of output data
distributed to 32 subscribers, and at 12 Mbit/s (BK3100 and BK3110) less
than 2 ms. This fulfills the requirement for a fast system response time.

System configurations and
device types

You can use PROFIBUS DP to implement mono-master or multi-master
systems, which gives you a high degree of flexibility as regards the system
configuration. Up to 126 miscellaneous devices (master or slaves) can be
attached to one bus. The bus couplers BK3xx0 permit you to select a