BK3xxx/LC3100

Fieldbus errors in the LC3100

I/O-RUN

BF

RUN

Meaning

Remedy

on

off

on

Operating state: RUN

Inputs are read and outputs are set.

Everything is operating correctly

on

on

on,
blinking

1. Bus activity, but slave is not yet
parameterised
2. Bus error in which the outputs

a.) become 0

b.) remain unchanged

- Start master
- Check parameters
(-> Diagnostics data, BF-LED)
- Check configuration
(-> Diagnostics data, BF-LED)

off

off

on

Terminal bus cycles synchronised
DP-watchdog switched off, no exchange
of data

PLC is in STOP mode

off

on

off,
blinking

No bus activity

- Start master
- Check bus cable

off

on

on

Bus error, reaction
Terminal bus cycles are stopped

- Start master
- Check parameters
(-> Diagnostics data, BF-LED)
- Check configuration
(-> Diagnostics data, BF-LED)



Run times and reaction times

Transfer of the signals from the input to the controller and from the
controller to the outputs requires a run time. This is composed of various
components. Transfer from the controller to the master, transfer through
the Profibus and transfer from the bus coupler to the outputs. This applies
analogously to the return distance.

Controller / Master




Please refer to the data provided by the master manufacturer for details of
the reaction time from the controller to the master. These times are
comparatively short and normally do not need to be considered.

The reaction time t

DP

on the Profibus is composed of the following. The

constants A, B and T

BYTE

depend on the baud rate.

7
T

DP

= Constant A

+ (Constant B + (Number of E/A-Byte x T

BYTE

))

[Slave 1]

+ (Constant B + (Number of E/A-Byte x T

BYTE

))

[Slave 2]

+ (Constant B + (Number of E/A-Byte x T

BYTE

))

[Slave 3]

+ ...

[Slave ]

+ (Constant B + (Number of E/A-Byte x T

BYTE

))

[Slave n]

Baud rate

Constant A
(in ms)

Constant B
(in ms)

T

BYTE

(in ms)

9,6 kBaud

64,5

25,6

1,15

19,2 kBaud

32,3

12,8

0,573

93,75 kBaud

6,6

2,62

0,118

187,5 kBaud

3,3

1,31

0,059

500 kBaud

1,6

0,49

0,022

1,5 MBaud

0,67

0,164

0,00733

3 MBaud

0,436

0,085

0,00367


6 MBaud

0,27

0,044

0,00183

12 MBaud

0,191

0,024

0,00092


i

Note

Pay attention to the special restrictions when using an ET200U or S5-95U
in one system. In certain circumstances, cycle times may be clearly
prolonged and more than 1.5 Mbaud is not possible.