32

BK3xxx/LC3100

You should also note that the terminating resistor requires a 5 V power
supply for optimal operation. This means that if the plug is removed from
the bus coupler, or the power supply of the bus coupler fails, the level at
the terminating resistor will vary, which may affect the data transfer.

Configuring the master

As explained above, the Profibus coupler sets up a data area containing
the input and output bytes. The assignments between the channels of the
bus terminals and the bits and bytes of the process image are carried out
by the bus coupler.

The Profibus master exchanges a coherent input and output data block
with each Profibus coupler. The correlation between the bytes in this data
block and the addresses of the process image is carried out by the master.
In the case of the IM308-C SPS master, this parametrization is supported
by the software COMWIN, and for the IM308-B by the software
COMET200. For other masters you should use the corresponding tools
provided by the manufacturer (see also the chapters Device master file
and Type file).


Support files for configuring
the master

Master / Software

Coupler

File

General for all Profibus
masters

BK3XX0

BUSKLEMN.BMP
BUSKLEMS.BMP




General for all Profibus
masters

BK3000
BK3010
BK3100
BK3110
BK3500
LC3100

BK30BECF.GSD
BK3010.GSD
BK31BECE.GSD
BK3110.GSD
BK3500.GSD
BK3110.GSD

COM PROFIBUS and COM
Profibus Windows software /
TYPDAT5X

BK3000
BK3010
BK3100
BK3110
BK3500
LC3100

BK3000AD.200
BK3010AD.200
BK3100AD.200
BK3110AD.200
BK3500AD.200
BK3110AD.200

IM308-B
COMET200

BK3000
BK3010
BK3100
BK3110
BK3500
LC3100

BK3000TD.200
BK3010AD.200
BK3100AD.200
BK3110AD.200
BK3500AD.200
BK3110AD.200



Quick start

When the coupler is started up, all the terminals are written into the process
image. The coupler then proceeds in accordance with the following rules:
first all the terminals with byte-oriented operation, then all the bit-oriented
terminals.

Byte oriented bus terminals

Bit oriented bus terminals

KL1501

KL10XX, KL11XX, KL12XX, KL17XX

KL2502

KL20XX, KL21XX, KL22XX, KL26XX
KL27XX

KL3XXX

KL4XXX

KL5XXX

KL6XXX

KL9110, KL9160, KL9210, KL9260