Baud rate – BECKHOFF BK3000 User Manual

Page 30

Advertising
background image

PROFIBUS coupler BK3xx0 in the PROFIBUS DP

30

BK3xxx/LC3100

BK3500

02

01

+ +

PE PE

RUN

BF

DIA

PROFIBUS

B

E

CK

H

O

F

F

24V

0V

00

X0

BK

35

00

Field Bus
Signal Input
Field Bus
Signal Output

Configuration
Interface

Address
Selector

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

Baud
rate

x1

x10

1

ON

2



Profibus fiber optic net

Characteristics

Characteristics

Topologiy

Subring

max. amount of
stations

93,75 kBaud: 13

187,5 kBaud: 12

500 kBaud: 12

1500 kBaud : 10

min./max.length
between two
stations

Coordinator – Station: Lmin = 1 m, Lmax = 34 m

Station – Station: Lmin = 1 m, Lmax = 25 m
Station – Coordinator: Lmin = 0 m, Lmax = 46 m

Bus connector

2 x HP Simplex connector (included)

APF (plastic)- fiber conductor (Z1101)

Baud rate

93,75; 187,5; 500; 1500 kBaud

Switch position

S1=0,S2=0; S1=0,S2=1; S1=1,S2=0; S1=1,S2=1



RS485
Fundamental
characteristics

RS-485

Data transfer
technology to the
Profibus standard

Network topology

Linear bus, active bus terminator at both ends, branch
lines are possible

Medium

Shielded twisted cable, shielding may be dispensed with in
suitable environments (electromagnetic compatibility)

Number of stations

32 stations in each segment without repeaters, extendible
to 127 with repeaters


Max. bus length

without repeaters

100 m at 12 Mbit/s

200 m at 1500 Kbit/s, up to 1.2 km at 93.75 Kbit/s

with repeaters

Using repeaters (line amplifiers) increases the max. bus
length to the order of 10 km. The number of possible
repeaters is at least 3 and may be up to 10, depending on
the manufacturer

Transfer rates

9.6, 19.2, 93.75, 187.5, 500, 1500 Kbit/s, up to 12 Mbit/s in
discrete steps

Plug

9-Pin D-Sub plug