2.2.3

Setup Software

2.2.3.1

Screen page PROFIBUS

This screen will only appear, if the PROFIBUS hardware is built into the servo amplifier. The screen
page displays the PROFIBUS-specific parameters, the bus status, and the data words in the trans-
mit and receive directions, as seen by the bus-master. This page is helpful when searching for
errors and commissioning the bus communication.

Baudrate:

The baud rate set by the PROFIBUS master.

PNO Identno.:

The PNO identification is the number for AX2000/2500 from the list
of ID-numbers set by the PROFIBUS user organization.

Address:

Station address of the amplifier (setting see p.8).

PPO type:

AX2000/2500 only supports PPO-type 2 of the PROFIDRIVE profile.

PROFIBUS Interface states:

Shows the present status of the bus communication. Data can only be
transferred across the PROFIBUS when the “Communication OK”
message is black (not shown in gray).

Input:

The last PROFIBUS object received by the master.

Output:

The last PROFIBUS object sent by the master.

The data for input/output are only transferred, if the threshold monitoring for the
AX2000/2500 has been activated in the master’s hardware configuration.

PROFIBUS for AX2000/2500

13

BECKHOFF

12/05

Installation / Setup