PNU 930: Selection Switch for Operating Mode

The “Selector for operating modes” is defined by the drive profile, and mirrors the operating modes
of the drive profile to the operating modes of the AX2000/2500. The following table shows a sum-
mary of the operating modes:

If process data are exchanged across the PROFIBUS, then the operating modes of the drive
profile must only be selected with PNU 930.

Operating

mode of

drive profile

Operating mode AX2000/2500
(ASCII command “OPMODE”)

Description

2

8

Positioning mode according to PROFIDRIVE profile

1

0

Digital speed control according to PROFIDRIVE profile

0

-

reserved

-1

1

Speed control, analog setpoint

-2

2

Torque control, digital setpoint

-3

3

Torque control, analog setpoint

-4

4

Position control, electronic gearing

-5

5

Position control, external trajectory

-6 to -15

-

reserved

-16

-

ASCII channel for expanded parameterization

-17 to -125

-

reserved

-126

-

Initial settings when amplifier is switched on

The individual operating modes are described in chapter 5.2. A change of operating mode can only
be undertaken in connection with the control word.

The operating mode must be changed according to the following sequence:

1.

Inhibit setpoints and process data
Bit 10 in the control word is set to 0, so that no new setpoints will be accepted by the
servo amplifier and no new control functions can be initiated. A new operating mode
can, however, be selected while a motion function is being performed.
The control word is only inhibited to the extent that the servo amplifier can always be
switched into a safe state.

2.

Select the new operating mode with PNU 930
The new operating mode is selected with parameter 930 through the parameter channel,
but not yet accepted.

3.

Set/receive the setpoints and actual values
Enter the corresponding setpoints in the setpoint area of the process data.
Here you must take note that the normalization and data formats depend on the operating
mode that is selected. The interpretation of the actual values is also altered
(see

Þ p. 15 and p. 37ff). The user program must respond accordingly.

4.

Enable the setpoints
Bit 10 of STW is set to 1. The setpoints are immediately accepted and processed.
The new actual values are output with the appropriate normalization and data format.

After switch-on or after a coldstart the servo amplifier is always in the safe operating mode.
In the safe operating mode (-126), no motion functions can be initiated via the PROFIBUS.
However, it is possible to perform motion functions with the the setup Software.
If the operating mode is changed, then motion functions can only be operated via the
PROFIBUS. If the operating mode is changed via another communication channel, then the
amplifier is emergency braked and the error F21 (Handling error, expansion card) is
signaled.

PROFIBUS for AX2000/2500

23