Programming, Programming with the hb service tool, 15 hb controller technical guide – Orion System HB Controller User Manual

Page 15: Hb controller status & setpoints

Advertising
background image

Programming

15

HB Controller Technical Guide

The other available module screens are listed below in the order that
they would appear as you scroll down.

Factory Options should not be accessed without contacting AAON

®

or WattMaster.

Warning: The Factory Options settings should only be ap-

plied when authorized by AAON

®

or WattMaster

Technical Support personnel. Serious damage to the

controller and/or HVAC unit could result from im-

proper use of the Factory settings.

HB Controller Status & Setpoints

The Status and Setpoint screens for the various modules are accessed by
selecting a specifi c module and pressing the ENTER key.

Main Status Screens

The Main Status Screen is accessed by selecting the Main Status Module
and pressing the ENTER key. This screen, as its name indicates, allows
you to view the Main Status screens for the HB controller. After the
ENTER key is pressed, the following screen will be displayed:

HVAC Mode

Line #2 displays one of the following HVAC Modes:

• Idle

• Venting

• Cooling

• Econo

Cooling

• Heating

• Dehumidify

• Econo

Dehumidify

• Fault

• Force

Press the down SELECT arrow key or up SELECT arrow key to move
forward or backward through the Main Status screens.

OAT Heat Lockout

Line #2 displays “YES” if the Outdoor Air Temperature is above the
Heating Lockout Temperature Setpoint.

OAT Cool Lockout

Line #2 displays “YES” if the Outdoor Air Temperature is below the
Cooling Lockout Temperature Setpoint.

OAT Temperature

Line #2 displays the current Outdoor Air Temperature.

SAT Temperature

Line #2 displays the current Supply Air Temperature.

Alarms

Line #2 displays “YES” if an alarm is active. To identify the active
alarm(s), press the ESC key, select the Alarm Module, and scroll through
the available alarms using the up and down SELECT arrow keys.

Program Date

Line #2 displays the Month/Day/Year that the HB Controller software
was created.

Programming with the HB Service Tool

Advertising