Programming, Programming with the hb service tool, 21 hb controller technical guide – Orion System HB Controller User Manual

Page 21

Advertising
background image

Programming

21

HB Controller Technical Guide

Heating Fan Off Delay

Description

Min.

Default

Max.

Fan Off Delay Period

1 Sec

120 Sec

180 Sec

The Heating Fan Off Delay is a factory setting and should not be
changed unless authorized to do so by WattMaster or AAON

®

Techni-

cal Support.

Auto Stage-Up Time

Description

Min.

Default

Max.

Auto Staging Up Delay

180 Sec

600 Sec

900 Sec

The Auto Stage-Up Time can be adjusted on this screen when you are
using a single-stage thermostat with a multi-stage HB unit.

Economizer Module Status Screens

The Economizer Module Status Screens are accessed by navigating to
the Economizer Module and pressing the ENTER key. The following
screen will then appear:

Select “Status” by pressing the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the
Economizer Module Status screens.

Economizer Current Position

Line #2 displays the current Economizer Position as a percent open
value.

Supply Air Temperature

Line #2 displays the current Supply Air Temperature.

Programming with the HB Service Tool

Heating Minimum Off Time

Description

Min.

Default

Max.

Minimum Off Time

60 Sec

60 Sec

900 Sec

Adjust the desired Heating Minimum Off Time and then press the
ENTER key.

Heating Minimum On Time

Description

Min.

Default

Max.

Minimum On Time

120 Sec

120 Sec

900 Sec

Adjust the desired Heating Minimum On Time and then press the
ENTER key.

Heating Stage-Up Delay

Description

Min.

Default

Max.

Staging Up Delay Interval

180 Sec

180 Sec

900 Sec

Adjust the desired Heating Stage-Up Delay time and then press the
ENTER key.

Heating Stage Down Delay

Description

Min.

Default

Max.

Staging Down Delay Interval

60 Sec

60 Sec

900 Sec

Adjust the desired Heating Stage Down Delay time and then press the
ENTER key.

Heat Safety Monitor Maximum Trips

Description

Min.

Default

Max.

Heat Safety Maximum Count

1

3

5

The Heating Safety Maximum Trips is a factory setting and should
not be changed unless authorized to do so by WattMaster or AAON

®

Technical Support.