Programming, Programming with the hb service tool, 25 hb controller technical guide – Orion System HB Controller User Manual

Page 25

Advertising
background image

Programming

25

HB Controller Technical Guide

Programming with the HB Service Tool

Force Mode Module Screens

The Force Mode Module screens are accessed by navigating to the
Force Mode Module screen and pressing the ENTER key. After pressing
ENTER, the following screen will appear:

Press the down SELECT arrow key until “Force” is on the top line
of the screen and then press the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the Force
Mode Module screens.

Force Time Limit

Description

Min.

Default

Max.

Force Mode Timer

1 Min

60 Min

240 Min

Adjust the desired time needed for forcing the HB Controller into the
Force Module Mode and then press the ENTER key.

Force Mode


Adjust to select “Start” and then press the ENTER key to enter Force
Mode. Adjust to select “Stop” and then press the ENTER key to end
Force Mode.

Fan Speed Force


Adjust to select “Low Speed” and then press the ENTER key to place
the Supply Fan in Low-Speed operation. Adjust to select “High Speed”
and then press the ENTER key to place the Supply Fan in High-Speed
operation.

Fan Signal Force

Adjust the Fan Signal Voltage signal up or down to speed up or slow
down the Supply Fan and then press the ENTER key.

Bad LLT


Line #2 displays “YES” when Condenser Fan Control is confi gured and
the Liquid Line Temperature Sensor is bad or missing.

High SAT Cutoff


Line #2 displays “YES” when the HB Controller is locked out in High
Supply Air Temperature Cutoff.

Low SAT Cutoff


Line #2 displays “YES” when the HB Controller is locked out in Low
Supply Air Temperature Cutoff.

OAT Cooling Lockout


Line #2 displays “YES” if the Outdoor Air Temperature is below the
Cooling Lockout Temperature setpoint.

OAT Heating Lockout


Line #2 displays “YES” if the Outdoor Air Temperature is above the
Heating Lockout Temperature setpoint.

Clogged Filter

Line #2 displays “YES” if there is a 24 VAC signal on the Clogged
Filter Input.