Programming, Programming with the hb service tool, 23 hb controller technical guide – Orion System HB Controller User Manual

Page 23

Advertising
background image

Programming

23

HB Controller Technical Guide

Programming with the HB Service Tool

CO2 Minimum Position with High-Speed Fan

Description

Min.

Default

Max.

Min. with High-Speed Fan

0%

5%

100%

Adjust the Economizer Minimum Position during High-Speed Supply
Fan operation when CO

2

levels are below the Minimum CO

2

setpoint

and then press the ENTER key.

CO2 Maximum Position with Low Speed Fan

Description

Min.

Default

Max.

Max. with Low-Speed Fan

0%

50%

100%

Adjust the Economizer Maximum Position during Low-Speed Supply
Fan operation when CO

2

levels are above the Maximum CO

2

setpoint

and then press the ENTER key.

CO Maximum Position with High-Speed Fan

Description

Min.

Default

Max.

Max. with High Speed Fan

0%

30%

100%

Adjust the Economizer Maximum Position during High-Speed Supply
Fan operation when CO

2

levels are above the Maximum CO

2

setpoint

and then press the ENTER key.

Exhaust Fan On with Low-Speed Fan

Description

Min.

Default

Max.

Low-Speed Supply Fan

0%

50%

100%

Adjust the Economizer Position during Low-Speed Supply Fan operation
that will activate the Exhaust Fan and then press the ENTER key.

Exhaust Fan On with High-Speed Fan

Description

Min.

Default

Max.

High-Speed Supply Fan

0%

30%

100%

Adjust the Economizer Position during High-Speed Supply Fan operation
that will activate the Exhaust Fan and then press the ENTER key.

CO2 Level Economizer Opens Above Minimum

Description

Min.

Default

Max.

Min. CO

2

0 PPM

900 PPM

2000 PPM

Adjust the Minimum CO

2

Level that will allow the Economizer to

Modulate above its minimum position and then press the ENTER key.

CO2 Level Economizer Opens to Economizer Maximum

Description

Min.

Default

Max.

Max. CO

2

0 PPM

1100 PPM

2000 PPM

Adjust the Maximum CO

2

Level that will allow the Economizer to Modu-

late open to its maximum position and then press the ENTER key.

Dehumidify Module Status Screens

The Dehumidify Module Status Screens are accessed by navigating to
the Dehumidify Module and pressing the ENTER key. Setpoints are
not available for the Dehumidify Module. After pressing ENTER, the
following screen will appear:

RH Terminal Active

Line #2 displays “YES” if there is a 24 VAC signal on the “RH”
terminal.

Fan Status

Line #2 displays the current Supply Fan Status. If the Supply Fan is on,
Line #2 displays either “Fan Low Speed” or “Fan High Speed.”

Fan Signal

Line #2 displays the current Supply Fan Analog Output Signal in DC
Volts.