Low Supply Air Temperature Cutoff

Description

Min.

Default

Max.

Supply Air Low Temperature

Limit Cut Off

32ºF

40ºF

80ºF

Adjust the Low Supply Air Temperature Cutoff and then press the
ENTER key. The value must be below the Economizer Oat Enable.

Cooling Minimum Off Time

Description

Min.

Default

Max.

Minimum Off Time

180 Sec

180 Sec

900 Sec

Adjust the desired Cooling Minimum Off Time and then press the
ENTER key.

Cooling Minimum On Time

Description

Min.

Default

Max.

Minimum On Time

300 Sec

300 Sec

900 Sec

Adjust the desired Cooling Minimum On Time and then press the
ENTER key.

Cooling Stage-Up Delay

Description

Min.

Default

Max.

Staging Up Delay Interval

180 Sec

180 Sec

900 Sec

Adjust the desired Cooling Stage-Up Delay time and then press the
ENTER key.

Cooling Stage Down Delay

Description

Min.

Default

Max.

Staging Down Delay Interval

60 Sec

60 Sec

900 Sec

Adjust the desired Cooling Stage-Down Delay time and then press the
ENTER key.

High Pressure Switch

Line #2 displays the current status of the High Pressure Switch. It will
only display “CLOSED” when Cooling Relay #1 relay is active and the
High Pressure Switch is operating correctly.

Cooling Module Setpoint Screens

The Cooling Module Setpoint Screens are accessed by navigating to
the Cooling Module screen and then pressing the ENTER key. The
following screen will then appear:


Press the down SELECT arrow key until “Setpoints” is on the top line
of the screen and then press the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the Cool-
ing Module Setpoint screens.

Cooling Stages Quantity

Description

Min.

Default

Max.

Cooling Stages

1

2

2

Adjust the quantity of Cooling Stages or Steps of Cooling and then
press the ENTER key.

Condenser Fan Control

Select “YES” for Condenser Fan Control if you are using a Liquid Line
Temperature Sensor and then press the ENTER key.

Outdoor Air Temperature Cooling Lockout

Description

Min.

Default

Max.

Cooling Lockout Temperature

32ºF

40ºF

80ºF

Adjust the Outdoor Air Temperature Cooling Lockout and then press
the ENTER key.