Programming, Programming with the hb service tool, 26 hb controller technical guide – Orion System HB Controller User Manual

Page 26

Advertising
background image

Zone

Zone

Programming

26

HB Controller Technical Guide

Programming with the HB Service Tool

Economizer Force


Adjust the Economizer percentage up or down to position the Econo-
mizer where needed and then press the ENTER key.

Return Air Bypass Force


Adjust the Return Air Bypass Damper percentage up or down to position
the Return Air Bypass where needed and then press the ENTER key.

Exhaust Fan Relay Force


Select “YES” to activate the Exhaust Fan Relay and then press the
ENTER key.

Condenser Fan Relay Force


Select “YES” to activate the Condenser Fan Relay and then press the
ENTER key.

Cooling Relay #1 Force


Select “YES” to activate Cooling Relay #1 and then press ENTER.

Cooling Relay #2 Force


Select “YES” to activate Cooling Relay #2 and then press ENTER.

Heating Relay #1 Force


Select “YES” to activate Heating Relay #1 and then press ENTER.

Heating Relay #2 Force


Select “YES” to activate Heating Relay #2 and then press ENTER.

Heating Relay #3 Force


Select “YES” to activate Heating Relay #3 and then press ENTER.

Force Mode Module Setpoint Screens

The Force Mode Module Setpoint screens are accessed by navigating to
the Force Mode Module screen. Press the down SELECT arrow key until
“Setpoints” is on the top line of the screen and then press the ENTER
key. After pressing ENTER, the following screen will appear:

Low-Speed Fan Signal

Description

Min.

Default

Max.

Low-Speed Fan Signal

1.0 VDC

3.0 VDC

10.0 VDC

Adjust the Low-Speed Supply Fan Signal and then press ENTER.

High-Speed Fan Signal

Description

Min.

Default

Max.

High-Speed Fan Signal

1.0 VDC

10.0 VDC

10.0 VDC

Adjust the High-Speed Supply Fan Signal and then press ENTER.

CO2 Minimum Position with Low-Speed Fan

Description

Min.

Default

Max.

Min. with Low-Speed Fan

0%

10%

100%

Adjust the economizer minimum position during Low-Speed Supply
Fan operation when CO

2

levels are below the Minimum CO

2

setpoint

and then press the ENTER key.