Programming, Programming with the hb service tool, 22 hb controller technical guide – Orion System HB Controller User Manual

Page 22

Advertising
background image

Zone

Zone

Programming

22

HB Controller Technical Guide

Programming with the HB Service Tool

Outdoor Air Temperature

Line #2 displays the current Outdoor Air Temperature.

Fan Status

Line #2 displays the current Supply Fan status. If the Supply Fan is on,
line #2 displays either “Fan Low Speed” or “Fan High Speed.”

Fan Signal


Line #2 displays the current Supply Fan Analog Output Signal in DC
Volts.

Exhaust Fan Relay

Line #2 displays “ON” when the Exhaust Fan Relay is active.

Carbon Dioxide Level

Line #2 displays the Current Carbon Dioxide levels, given in parts per
million.

Economizer Change Over Switch


Line #2 displays “CLOSED” if there is a 24 VAC signal on the Econo-
mizer Changeover Switch input. This signal is provided by an Enthalpy
controller to enable the economizer for free Cooling.

Economizer Module Setpoint Screens

The Economizer Module Setpoint Screens are accessed by navigating
to the Economizer Module and then pressing the ENTER key. The fol-
lowing screen will then appear:

Press the down SELECT arrow key until “Setpoints” is on the top line
of the screen and then press the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the Econo-
mizer Module Setpoint screens.

Economizer Confi guration

Description

Min.

Default

Max.

Outdoor Air Enable Temp

33ºF

55ºF

65ºF

Select either “Has Economizer” or “No Economizer” and then press the
ENTER key. The value must be greater than the OAT Lockout.
.

Outdoor Air Temperature Enable

Description

Min.

Default

Max.

Outdoor Air Enable Temp

33ºF

55ºF

65ºF

Adjust the Outdoor Air Temperature to enable Economizer Free Cooling
and then press the ENTER key.

OAT Changeover to Mechanical Cooling

Description

Min.

Default

Max.

ECS OAT Enable Temp

55ºF

65ºF

75ºF

Adjust the Outdoor Air Temperature that will allow supplemental Me-
chanical Cooling during ECS Economizer operation and then press the
ENTER key.

CO2 Minimum Position with Low-Speed Fan

Description

Min.

Default

Max.

Min. with Low-Speed Fan

0%

10%

100%

Adjust the Economizer Minimum Position during Low-Speed Supply
Fan operation when CO

2

levels are below the Minimum CO

2

setpoint

and then press the ENTER key.