HB Controller Technical Guide
Condenser Fan Control Setpoints
Description
Min.
Default
Max.
Liquid Line Cut Out Temperature
75ºF
85ºF
95ºF
Liquid Line Cut In Temperature
95ºF
105ºF
115ºF
Table 12: Condenser Fan Control Setpoints
Miscellaneous Control Setpoints
Description
Min.
Default
Max.
Force Mode Timer
1 Min
60 Min
240 Min
Table 13: Miscellaneous Control Setpoints