Mhgrv module settings, Optional mhgrv module settings, Supply air temperature reset limit – Orion System HB Controller User Manual

Page 34: Zone, Figure 9: dip switch setting instructions, Set the setpoint dip switch to 55° f

Advertising
background image

Zone

Zone

MHGRV Module Settings

34

HB Controller Technical Guide

Supply Air Temperature

You can set the desired Discharge Air Temperature Setpoint using the
DIP Switch labeled SETPOINT on the MHGRV Module. See Figure 9
for location and DIP Switch setting instructions. The MHGRV Module
will allow you to set a Supply Air Temperature Setpoint between 50° F
and 100° F. If a value of less than 50° F is set, the controller will default
to a 50° F Supply Air Temperature Setpoint. A value greater than 100°
F will cause the unit to default to a 100° F Supply Air Temperature
Setpoint.

Supply Air Temperature Reset Limit

You can reset the Supply Air Temperature Setpoint by supplying a 0-10
VDC control signal to the Reset Input (MHGRV RESET) terminal on
the HB controller board. The reset range is determined by the setting
confi gured on the DIP Switch labeled “RESET LIMIT.” See Figure 9
for location and setting instructions. The controller will reset the Sup-
ply Air Temperature Setpoint from the value set on the SETPOINT DIP
Switch to the value set on the RESET LIMIT DIP Switch as the Reset
Input (RST IN) signal is increased from 0 Volts to 10 Volts.

Example:
We want the Discharge Air Temperature Setpoint to increase from 55° F
when the Reset Input signal is at 0 Volts to 75° F when the Reset Input
signal is at 10 Volts.

Set the SETPOINT DIP Switch to 55° F

Set the RESET LIMIT DIP Switch to 75° F

The discharge air temperature will now increase from 55° F to 75° F as
the Reset Input voltage signal ramps from 0 Volts to 10 Volts.

Note: It is possible to create a “reverse acting” control sequence.

Using the temperatures from the example above by set-
ting the SETPOINT DIP Switch to 75

° F and the RESET

LIMIT DIP Switch to 55

° F, the reset would be reverse

acting. In this case, the controller will maintain a 75

° F

discharge temperature when the Reset Input signal is at
0 Volts and will reduce to 55

° F when the Reset Input

signal is at 10 Volts.

Optional MHGRV Module Settings

Figure 9: DIP Switch Setting Instructions

DIP Switch Setting Shown

Is For A Setpoint Of 53

DIP Switch Setting Shown

Is For A Setpoint Of 94

ADD

ADD

32 + 16 + 4 + 1 = 53

64 + 16 + 8 + 4 + 2 = 94

All Rocker Switches Depressed

In the Direction Of The ADD Arrow

Are Added Together To Total The Setpoint

HBl DIP Switch

Detail View

1

1

F

O

F

F

O

F

ADD

SETPOINT

0-10 VDC
Supply Air
Temp Reset
Signal

RESET

LIMIT

4

4

2

2

16

16

8

8

64

64

32

32

128

128

MOD HGR

EXTERNAL

INTERNAL

LD3

LD2

LD1

JO2

JO1

D1

C3

R4

VR1

Q1

C2

Q8

D20

K2

R70

R46

R48

R50

C21

R31

R33

LM358

9936

U3

C35

LM358

9936

Q9

D19

C36

D21

OFF

D2

U7

C7

RESET

PROGRAM

SOCEKT

128

LIMIT

32

64

16

8

RN3

P1

C1

C2

U4

RN1

P2

D1

C5

R4

C10

R5

R6

C11

SERIAL #

OFF

SETPOINT

4

2

1

128

64

ADD

32

16

8

4

2

1

C3

X1

C9

C8

U2

REV 1

YS101988

RN2

HB MHGR

LED2

R2

R3

R1

LED1

VA
LV
E

HGR

U5

MADE

IN
THE

U

SA

C4

L1

C12

GND

RH

Y1

G

GND

R

SAT

POS

POS

GND

GND

RAB

RAB

TB2

RESET

RESET

ECONO

ECONO

MHGRV

MHGRV

TB1

Advertising