HB Controller Technical Guide

Programming with the HB Service Tool

RAB Position


Line #2 displays the current Return Air Bypass damper position.

Cooling Relay #1

Line #2 displays “ON” if Cooling Relay #1 is active.

Cooling Relay #2

Line #2 displays “ON” if Cooling Relay #2 is active.

OAT Temperature

Line #2 displays the current Outdoor Air Temperature.

Economizer Current Position

Line #2 displays the current Economizer Position as a percent
open value.

Supply Air Temperature


Line #2 displays the current Supply Air Temperature.

Liquid Line Temperature


Line #2 displays the current Liquid Line Temperature.

Condenser Fan Relay


Line #2 displays “ON” if the Condenser Fan Relay is active.

Alarm Module Status Screens

The Alarm Module Status Screens are accessed by navigating to the
Alarm Module and pressing the ENTER key. Setpoints are not available
for the Alarm Module. After pressing ENTER, the following screen
will appear:

HSM Lockout


Line #2 displays “YES” when the Heat Safety Monitor has tripped more
than the HSM Max Trips setpoint.

HPS Fault


Line #2 displays “YES” when the High Pressure Switch is open and a
Cooling Relay is active.

LPS Lockout


Line #2 displays “YES” when the Low Pressure Switch has tripped
more than the LPS Max Trips setpoint.

Bad OAT Sensor


Line #2 displays “YES” when the Outdoor Air Temperature Sensor is
bad or missing.

Bad SAT Sensor

Line #2 displays “YES” when the Supply Air Temperature Sensor is
bad or missing.