Appendix, 37 hb controller technical guide – Orion System HB Controller User Manual

Page 37

Advertising
background image

Appendix

37

HB Controller Technical Guide

Appendix

The HB controller has many setpoints that are user-adjustable. This
adjustability allows the installer complete control of all major unit
operating characteristics during the setup and commissioning phase
of the HB unit installation. It also gives a service technician the ability
to change setpoints to monitor and record unit operation to determine
if the unit is functioning as specifi ed. The tables that follow show the
available setpoints for each classifi cation or control group provided on
the HB controller.

Supply Fan Control Setpoints

Description

Min.

Default

Max.

Adj. Two-Speed Fan

-

Two-Speed Fan

-

Low-Speed Fan Signal

1.0 VDC

3.0 VDC

10.0 VDC

High-Speed Fan Signal

1.0 VDC

10.0 VDC

10.0 VDC

Table 5: Supply Fan Control Setpoints

Cooling Control Setpoints

Description

Min.

Default

Max.

Cooling Stages

1

2

2

Minimum Off Time

180 Sec

180 Sec

900 Sec

Minimum On Time

300 Sec

300 Sec

900 Sec

Staging Up Delay Interval

180 Sec

180 Sec

900 Sec

Staging Down Delay Interval

60 Sec

60 Sec

900 Sec

Low Pressure Delay Period

5 Sec

30 Sec

60 Sec

Low Pressure Safety

5 Sec

5 Sec

30 Sec

Low Pressure Max. Trip Point

1

3

5

Fan Off Delay Period

1 Sec

45 Sec

120 Sec

Auto Staging Up Delay

180 Sec

600 Sec

900 Sec

Dehumidify Staging Up Delay

180 Sec

600 Sec

900 Sec

Table 6: Cooling Control Setpoints

Heating Control Setpoints

Description

Min.

Default

Max.

Heating Stages

1

3

3

Minimum Off Time

60 Sec

60 Sec

900 Sec

Minimum On Time

120 Sec

120 Sec

900 Sec

Staging Up Delay Interval

180 Sec

180 Sec

900 Sec

Staging Down Delay Interval

60 Sec

60 Sec

900 Sec

Heat Safety Maximum Count

1

3

5

Fan Off Delay Period

1 Sec

120 Sec

180 Sec

Auto Staging Up Delay

180 Sec

600 Sec

900 Sec

Table 7: Heating Control Setpoints

Temperature Control Setpoints

Description

Min.

Default

Max.

Cooling Lockout Temperature

32ºF

40ºF

80ºF

Heating Lockout Temperature

40ºF

80ºF

120ºF

Supply Air High Temperature

Limit Cutoff

120ºF

150ºF

170ºF

Supply Air Low Temperature

Limit Cutoff

32ºF

40ºF

80ºF

Table 8: Temperature Control Setpoints

Economizer Control Setpoints

Description

Min.

Default

Max.

Econo Confi g

No

Economizer

Max. CO

2

0 PPM

1100 PPM

2000 PPM

Min. CO

2

0 PPM

900 PPM

2000 PPM

Outdoor Air Enable Temp

33ºF

55ºF

65ºF

ECS OAT Enable Temp

55ºF

65ºF

75ºF

Table 9: Economizer Control Setpoints

Exhaust Fan Control Setpoints

Description

Min.

Default

Max.

Low-Speed Supply Fan

0%

50%

100%

High-Speed Supply Fan

0%

30%

100%

Table 10: Exhaust Fan Control Setpoints

Min. Damper Reset Position Setpoints

For Adjustable Two-Speed Fan/CO

2

Description

Min.

Default

Max.

Max. with Low-Speed Fan

0%

50%

100%

Min. with Low-Speed Fan

0%

10%

100%

Max. with High-Speed Fan

0%

30%

100%

Min. with High-Speed Fan

0%

5%

100%

Table 11: Minimum Damper Reset Setpoints