Condenser Fan Deactivation Temperature

The Condenser Fan Deactivation Temperature is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON

®

Technical Support.

Auto Stage-Up Time

Description

Min.

Default

Max.

Auto Staging Up Delay

180 Sec

600 Sec

900 Sec

The Auto Stage-Up Time can be adjusted on this screen when you are
using a single-stage thermostat with a multi-stage HB unit.

Heating Module Status Screens

The Heating Module Status Screens are accessed by navigating to the
Heating Module screen and pressing the ENTER key. The following
screen will then appear:


Select “Status” by pressing the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the Heat-
ing Module Status screens.

Heating Stage 1 Energized

Line #2 displays “YES” if there is a 24 VAC signal on HB Controller
terminal “W1.”

Heating Stage 2 Energized


Line #2 displays “YES” if there is a 24 VAC signal on HB Controller
terminal “W2.”

Low Pressure Switch Delay

Description

Min.

Default

Max.

Low Pressure Delay Period

5 Sec

30 Sec

60 Sec

The Low Pressure Switch Delay time is a factory setting and should
not be changed unless authorized to do so by WattMaster or AAON

®

Technical Support.

Low Pressure Switch Safety Delay

Description

Min.

Default

Max.

Low Pressure Safety

5 Sec

5 Sec

30 Sec

The Low Pressure Switch Safety Delay time is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON

®

Technical Support.

LPS Maximum Trips

Description

Min.

Default

Max.

Low Pressure Max. Trip Point

1

3

5

The Low Pressure Switch Max Trips is a factory setting and should
not be changed unless authorized to do so by WattMaster or AAON

®

Technical Support.

Cooling Fan Off Delay

Description

Min.

Default

Max.

Fan Off Delay Period

1 Sec

45 Sec

120 Sec

The Cooling Fan Off Delay is a factory setting and should not be
changed unless authorized to do so by WattMaster or AAON

®

Techni-

cal Support.

Condenser Fan Activation Temperature

The Condenser Fan Activation Temperature is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON

®

Technical Support.