Troubleshooting

36

HB Controller Technical Guide

Using LEDs To Verify Operation

The HB controller is equipped with LEDs that can be used as very
powerful troubleshooting tools. The HB controller circuit board has
three differently colored LEDs. See Figure 11 for the various LED
locations. The Red LED is used to indicate fault conditions. The Yel-
low LED indicates the mode of operation the HB controller is currently
operating in. The Green LED indicates the power and communications
status of the HB controller.

LD3

LD2

LD1

GND

SAT

POS

GND

RAB

TB2

RESET

ECONO

MHGRV

TB1

LD1 - Red LED

HB Controller Board

LD2 - Yellow LED

LD3 - Green LED

Figure 10: HB Board LED Locations

One LED blink is defi ned as a 1-second LED ON period immediately
followed by a 1-second LED OFF period. After each series of blinks is
completed, the LED will power off for 3 seconds and then repeat the
series of blinks. The various blink codes and their meanings are defi ned
in the tables that follow.

Red LED

LED

Blinks

Fault Condition Description

1

Heat Safety Lockout

2

High Pressure Fault

3

Low Pressure Lockout

4

Bad Supply Air Temperature Sensor

5

Bad Outdoor Air Temperature Sensor

6

Bad Liquid Line Temperature Sensor

7

Clogged Filter Switch

Notes:
1. When no fault exists, the red LED will be off.
2. Heat Safety Lockout (1 blink) is the highest priority. Clogged
Filter Switch (7 blinks) is the lowest priority.

Table 2: Red LED Blink Codes

HB Controller Fault Condition Operation

If the Red LED indicates a Bad Outdoor Air Temperature Sensor, Heating
Mode will operate, but Cooling Mode will be disabled until the sensor
problem is fi xed.

If the Red LED indicates a Bad Supply Air Temperature Sensor, Heating
and Cooling Modes will continue to operate, but all Reheat functions
will be disabled during Dehumidifi cation and Economizer Modes.

If the Red LED indicates a Bad Liquid Line Temperature Sensor, the
Condenser Fan will run continuously any time the Cooling Relays are
energized.

Yellow LED

LED

Blinks

Mode Indication Description

1

Vent Mode (Fan Only)

2

Heating Mode

3

Cooling Mode

4

Economizer Mode

5

Dehumidifi cation Mode

6

Economizer Dehumidifi cation Mode

Table 3: Yellow LED Blink Codes

Green LED

LED

Blinks

Power/Communications Description

1

Power Indicator (No Communications)

2

HSS Communications

3

MHGRV Communications

4

MHGRV/HSS Communications

Table 4: Green LED Blink Codes