Reheating

Desired charging temperature for the hot water

storage tank.

Set temperature to which conventional reheating

should heat the storage tank to ensure comfort. If

there is a solar yield, the storage tank can become

substantially warmer. The maximum temperature

for solar charging can be modified under Settings/

Solar/Storage tank.

For efficiency reasons, the lowest possible set tem-

perature should be selected. If the available quan-

tity of hot water is insufficient, the value should be

increased. Pay attention to the maximum tempera-

ture of the heat generator while doing so.

Select the storage tank set temperature with the

rotary knob and confirm with "OK".

Fig. 40: Reheating

Menu item

Parameter

Factory setting

Storage tank

set temp.

40°C - 65°C

Factory recom-

mendation

45°C

Press "Next".

Hot water circulation

If there is a hot water circulation pump in the

building, which you are intending to operate in an

energy-saving manner using the controller, this

function must be activated (select with the rotary

knob and confirm with "OK").

Fig. 41: Hot water circulation

Menu item

Parameter

Factory setting

Hot water

circulation

Deactivated

As required

Activated

Press "Next".