System separation

Activation if the floor heating cycle is separated by

a heat exchanger.

To control a separate heating cycle pump with a

system separation by means of a heat exchanger,

the function System separation FBHmust be acti-

vated (select with the rotary knob and confirm with

"OK").

Fig. 50: Activating the system separation

Menu item

Parameter

Factory setting

System sep-

aration FBH

Deactivated

Deactivated

Activated

For optimal configuration of the heating curve

parameters, the heating load calculation and/or

energy consumption must be taken into account.

Differences between the installed parameters and

the design of the actual building can cause the

heat pump to run inefficiently.

Operating the heating cycle with a fixed value is

not recommended, as it will cause the heat pump

to operate inefficiently.

Heating cycle for radiator heating

Activate if a heating cycle with radiators is

installed. (select with the rotary knob and confirm

with "OK")

Fig. 51: Activating the heating cycle for radiator

heating

Menu item

Parameter

Factory setting

Heating

cycle for

radiator

heating (HK)

Deactivated

Deactivated

Activated

Press "Next".

Setting heating cycle mode

This is where you can select between the different

heating cycle modes. The choice is between con-

trol according to the set "Heating curve" and

"Fixed value control" (select with the rotary knob

and confirm with "OK").

Menu item

Parameter

Factory setting

Heating

cycle mode

for HK active

Heating curve

According to

design

Fixed value

10°C - 40°C

Press "Next".

Heating-curve heating cycle mode

The heating curve can be adjusted in three points,

according to the structure and location-related con-

ditions of the building:

Base point:

The base point corresponds to the minimum set

temperature of the heating water at an outside

temperature of 20°C. If the heating is too cold at

relatively high outside temperatures (trans-sea-

sonal period), the base point should be set higher.