REMKO WPM-Smart-Control-Manual for specialists-WKF-085 User Manual
Page 29
Impulse-guided circulation - Disable switch-on
After the running time of the circulation pump, the
pump cannot be started again while disable switch
on is active. This prevents unnecessary permanent
operation of the pump in the case of continuous
dispensing. If the hot water cools too much while
disable switch-on is active, the time should be
shortened.
To set the desired time, select it with the rotary
knob and confirm the entry with "OK".
Fig. 44: Impulse-guided circulation - Setting dis-
able switch-on
Menu item
Parameter
Factory setting
Impulse-
guided circu-
lation - Dis-
able switch-
on
1 min - 15 mins
5 mins
Press "Next".
Temperature-guided circulation
Desired set temperature for temperature-guided
circulation.
This should be set at least 5°C below the set tem-
perature for reheating the hot water storage tank,
or even lower for efficiency reasons.
To set the desired temperature, select it with the
rotary knob and confirm the entry with "OK".
Menu item
Parameter
Factory setting
Tempera-
ture-guided
circulation
25°C - 65°C
35°C
Press "Next".
Heating cycle for panel heating
Optionally, you can activate or deactivate the
"Panel heating" function. Activate the heating cycle
for panel heating if wall or floor heating is installed.
If there is a system separation in the panel heating,
it must also be activated (select with the rotary
knob and confirm with "OK").
Fig. 45: Activating the panel-heating heating cycle
Menu item
Parameter
Factory setting
Heating
cycle for
panel
heating (FB)
Deactivated
Deactivated
Activated
Press "Next".
Setting heating cycle mode
This is where you can select between the different
heating cycle modes. The choice is between con-
trol according to the set "Heating curve" and
"Fixed value control" (select with the rotary knob
and confirm with "OK").
Menu item
Parameter
Factory setting
Heating
cycle mode
with FB
active
Heating curve
According to
design
Fixed value
10°C - 40°C
Press "Next".
29