REMKO WPM-Smart-Control-Manual for specialists-WKF-085 User Manual

Page 33

Advertising
background image

Building

type

Heat retention ability

Recom-

mended value

Light

Low heat retention ability, e.g. prefab / wood-frame houses

approx. 10h

Medium

Moderate heat retention ability, e.g. house made from hollow blocks

approx. 20h

Heavy

High heat retention ability, e.g. brick house

approx. 30h

Very heavy

Very high heat retention ability, e.g. exterior and interior walls > 30cm

approx. 60h

Passive

Well-insulated, e.g. zero-energy housing

approx. 100h

Fig. 55: Setting the building time constant

Menu item

Parameter

Factory setting

Building time

constant

0 - 100 h

According to

design! - 10 h

Press "Next".

Setting the standard heating load

Set the standard heating load (select with the

rotary knob and confirm with "OK"). The standard

heating load is obtained by multiplying the specific

heating load by the living area to be heated. You

can calculate the standard heating load from the

following table.

Building performance requirements

Year of construction

Specific heating load

Up to 1970, uninsulated

120 - 180 W/m

2

1977 to 1984

70 - 100 W/m

2

1985 to 1995

50 - 70 W/m

2

New build, EnEv

40 - 50 W/m

2

New build, KfW 40/60

20 - 30 W/m

2

Zero-energy house

10 - W/m

2

Fig. 56: Setting the standard heating load

Menu item

Parameter

Factory setting

Standard

heating load

0 - 25 kW

According to

design! - 14.0

kW

Press "Next".

33

Advertising