Menu item

Parameter

Factory setting

Control panel address

Control panel 1-3

Control panel 1

Country

Deutschland - Slovensko

Deutschland

Load setting

Accept the parameters

Saving process

Language

Deutsch - Polski

Deutsch

Time zone

Var. time zones possible

Winter + 1(CET) (for Europe)

Date setting

Year / Month / Day

Current date setting

Time setting

Hours / Minutes

Current time setting

Activate heat pump

Activated / Deactivated

Activated

Operating mode

Monoenergetic / Bivalent

alternative

Monoenergetic / Enable as required

Domestic water heating

Activated / Deactivated

Activated

Storage tank set temperature

"40°C - 65°C"

45°C

Hot water circulation

Activated / Deactivated

Deactivated

Circulation type

Impulse or Temperature

Impulse

Circulation running time

1 min - 15 mins

5 mins

Disable switch-on

1 min - 15 mins

5 mins

Circulation type

Impulse or Temperature

Temperature

Circulation set temp.

"25°C - 65°C"

35°C

Area-heating heating cycle

Activated / Deactivated

Following, as required

Area-heating heating cycle

Deactivated

No other parameters

Area-heating heating cycle

Deactivated

Parameter as required

Heating cycle mode

Heating curve / Fixed value

Heating curve

Heating-curve base point

"15°C - 25°C"

20°C (or according to design)

Standard inlet temperature

"28°C - 90°C"

35°C (or according to design)

Standard outside temperature "0°C - 20°C"

According to design or locale

Standard inlet temperature

"28°C - 90°C"

35°C (or according to design)

Standard outside temperature "0°C - 20°C"

According to design or locale

Heating cycle radiators

Activated / Deactivated

As required

Heating cycle radiators

Activated

Following parameters, as required

Heating cycle mode

Heating curve / Fixed value

Heating curve

Heating-curve base point

"15°C - 35°C"

20°C (or according to design)

Standard inlet temperature

"40°C - 90°C"

45°C (or according to design)

Standard outside temperature "0°C - 20°C"

According to design or locale

Building time constant

"0 h - 100 h"

10 h

Standard heating load

"0 kW - 25 kW"

According to design or heating load calcu-

lation