Remko smart wp manager – REMKO WPM-Smart-Control-Manual for specialists-WKF-085 User Manual
Page 66
"Settings" menu item (continued) - Expert
Authorisa-
tion level
Level 2 menu
item
Level 3 menu item
Level 4 menu item
Info
Heating /
cooling
Building adaptation
Building time constant
You can find
many of the indi-
vidual info texts
about the level
2-4 menu items
on your Smart-
Control
Standard heating load
Inertia of the heating curve
Mode
Room climate mode
Difference from cooling
limit
Difference from heating
limit
Floor screed drying func-
tion
After the floor screed
function we recommend
this function manually to
finish by deactivating!
Floor screed drying func-
tion status
Start / end temperature
Max.temperature
Heating phase increment
Drying time
Time at high temperatures
Incremental cooling phase
Time at low temperatures
Cooling
Cooling curve adjustment
Time programme
Setpoint increase
Room unit
Dewpoint monitoring
Cooling down (outside
temperature reference)
Floor screed function
Description
Value range
Factory setting
Customer
system
Floor screed function status
Activated / Deactivated
Deactivated
Start / end temperature
"10°C - 50°C"
20 °C
Max. temperature
"20°C - 50°C"
35°C
Incremental heating phase
0.0 K - 10.0 K
5.0 K
Drying time
0.0 h - 192 h
24 h
Time at high temperature
0.0 h - 192 h
96 h
Incremental cooling phase
0.0 K - 10.0 K
5.0 K
Time at low temperature
0.0 h - 192 h
24 h
REMKO Smart WP MANAGER
66