Heating-curve heating cycle mode

The heating curve can be adjusted in three points,

according to the structure and location-related con-

ditions of the building:

Base point:

The base point corresponds to the minimum set

temperature of the heating water at an outside

temperature of 20°C. If the heating is too cold at

relatively high outside temperatures (trans-sea-

sonal period), the base point should be set higher.

Standard inlet temperature:

the standard inlet temperature corresponds to the

set temperature of the heating water at the

standard outside temperature in the building loca-

tion. If the heating is not warm enough at low out-

side temperatures, the standard inlet temperature

should be increased.

Standard outside temperature:

the standard outside temperature is dependent on

the regional location of the building. Please consult

your heating installer.

2

1

4

3

Fig. 46: Heating curve adjustment

1: Temperature of the heating water in °C

2: Inlet temperature heating curve

3: Return flow heating curve

4: Outside temperature in °C

Setting the heating curve:

- Activate the base point with the right softkey, set

with the rotary knob and conform with the right

softkey.

Fig. 47: Setting the base point

- The standard inlet temperature and the outside

temperature are set using the same procedure.

Fig. 48: Setting the standard inlet temperature

Fig. 49: Setting the outside temperature

Fixed-value-control heating cycle mode

Specify the set temperature for fixed value control

(select with the rotary knob and confirm with "OK").

The heating cycle is kept permanently at this tem-

perature in fixed value control.

Press "Next".