Remotec ZTS-110 V3.14 User Manual

Page 18

Advertising
background image

18

Note: 
Explanations of Swing and Differential set point 

 

HEAT mode: thermostat controls the temperature according to the following diagram 









 

Example for Heating: (Set point = 70 °F, Swing = 1 °F, Differential = 2 °F) 

 

 

=> 1st stage heater turns on when room temp is 69 °F and off at 71 °F.   

 

 

=> 2nd stage heater turns on when room temp is 67 °F and off at 70 °F. 

 

COOL Mode: 

thermostat controls the temperature according to the following diagram 








 

Example for Cooling: (Set point = 80 °F, Swing = 1 °F) 

 

 

=> Cooler turns on when room temp is 81 °F and off at 79 °F.   

 

AUTO: thermostat controls the temperature according to the following diagram 










 

Output

Set point

Temperature

Swing

1

st

Turn off

1

st

Turn on

Off

Heat

2

nd

Turn on

2

nd

Turn off

Diff

SD= switch differential

Swing

Set point

Temperature

Turn off

Turn on

Off

Cool

Swing

swing

Dead band

Output

Heat Set point

Temperature

1

st

Turn off

1

st

Turn on

Off

Heat

2

nd

Turn on

2

nd

Turn off

Cool Set point

swing

Diff

Advertising