Support for Association Groups 

ZTS‐110 supports 3 association groups. 

 

Association group_1   

(Heat pump) 

Association group_2 

(Compressor) 

Association group_3 

(Auto Report) 

Heating mode 

ON 

(basic set command 0xFF)

OFF 

(basic set command 0x00) 

‐ 

Cooling mode 

OFF 

(basic set command 0x00)

ON 

(basic set command 0xFF) 

‐ 

OFF 

OFF 

(basic set command 0x00) 

OFF 

(basic set command 0x00) 

‐ 

 

Association group_3:  (Auto report) 

z

Association group_3 is used to report status change to gateway. 

(Only gateway or controller can be assigned in this association group) 

ZTS‐110 will trigger AUTO report function if one of below status is changed.   

I.

Operation mode (Off, Heat, Cool, Auto)   

II.

Operation state (Heat on or off, Cool on or off)   

III.

Fan mode (Auto, Auto low)   

IV.

Fan state (Fan on or Fan off) 

V.

Heat set point (report in precision 1 after decimal, e.g. 21.1

o

C ) 

VI.

Cool set point (report in precision 1 after decimal, e.g. 23.3

o

C ) 

VII. Current room temperature (report in precision 1 after decimal, e.g. 24.0

o

C)   

(It will trigger room temperature report if there is 4

o

F or 2

o

C (default) differ from last report. 

You can change this setting by set the configuration parameter)   

Note:   

Total 5 devices (nodes) can be assigned in total 3 association groups. Below table lists out the devices 

(nodes) allocations in the 3 association groups.   

Case no. 

No. of Node ID in 

Association Group_1 

No. of Node ID in 

Association Group_2 

No. of Node ID in 

Association Group_3 

Case 1 

1 (AUTO report) 

Mode 

Association group 