Remotec ZTS-110 V3.14 User Manual

Page 36

Advertising
background image

36

Upper limit of heat set point 

 

(Advance user can limit the 

upper heat set point in order to 

have energy saving) 

6 (0x06) 

Unit in C:   

Range from 5

o

C to [(37

o

C) ‐ (dead band)] 

Range from 50 (0x0032) to 355 (0x0163) 

Example 28

o

C; input = 280 (0x0118) 

Unit in F:   

Range from 41

o

F to [(99

o

F) ‐ (dead band)] 

Range from 410 (0x019A) to 960 (0x03C0) 

Example 82

o

F; input = 820 (0x0334) 

Default = (99

o

F) ‐ (dead band) 

Lower limit of cool set point 

 

(Advance user can limit the 

lower cool set point in order to 

have energy saving) 

7 (0x07) 

Unit in C:   

Range from [(5

o

C) + (dead band)] to 37

o

Range from 65 (0x0041) to 370 (0x0172) 

Example 20

o

C; input = 200 (0x00C8) 

Unit in F:   

Range from [(41

o

F) + (dead band)] to 99

o

Range from 440 (0x01B8) to 990 (0x03DE) 

Example 68

o

F; input = 680 (0x02A8) 

Default = (41

o

F) + (dead band) 

Easy Mode 

8 (0x08) 

0 (0x00) = Disable   

1 (0x01) = Enable, default 

Time format 

9 (0x09) 

0 (0x00) = 24 hours 

1 (0x01) = 12 hours (am / pm), default 

Repeat basic set counter 

(Association Group A and B 

only) 

10 (0x0A) 

Value(X) 

0 (0x00), 3 (0x03) to 255 (0xFF) 

0 (0X00) = Disable, default 

3 (0x03) to 255 (0xFF) minutes     

(Thermostat sends “Basic Set” command to 

its association node repeatedly in every X 

minutes) 

Trigger AUTO report if room 

temperature is different from 

last report. 

(It will report room 

temperature only) 

 

*User can use this function to 

enhance batteries service life. 

11 (0x0B) 

0 (0x00) = disable AUTO report if room 

temperature is different from last report. 

 

AUTO report if room temperature is 

different from last report. 

Delta change is >= 

1 (0x01) = 1

o

F (0.5

o

C) 

2 (0x02) = 2

o

F (1.0

o

C) 

3 (0x03) = 3

o

F (1.5

o

C) 

4 (0x04) = 4

o

F (2.0

o

C), default 

5 (0x05) = 5

o

F (2.5

o

C) 