TE Technology TC-36-25-RS485 User Manual

Page 28

Advertising
background image

 

28

2.6

ALARMS 
The alarm status and controls are viewed and set in this section. 

 
2.6.1 ALARM STATUS 

Any alarm that occurs in the controller whose address is in the address box will be displayed in the alarm status 
box.  When there is an active alarm the ALARM indicator light will blink. 
The possible alarm conditions are:               

 

HIGH ALARM: the temperature is greater than the HIGH ALARM SETTING 
LOW ALARM: the temperature is lower than the LOW ALARM SETTING 
COMPUTER CONTROLLED ALARM: the user has activated the alarm relay via the software 
OVER CURRENT DETECTED: the TE device attempted to draw more current than allowed the OVER CURRENT SET 
OPEN INPUT1: there is a problem with the primary temperature sensor 
OPEN INPUT2: there is a problem with the secondary temperature sensor 
DRIVER LOW INPUT VOLTAGE: the controller does not have a high enough voltage to properly operate 

 
2.6.2 ALARM MODE 

a) FIXED VALUE ALARMS: permits the setting of a fixed, absolute temperature either above or below the sensor 

temperature or both. 

b) COMPUTER CONTROLLED: provides for user activation of the alarm relay via the computer software. This is 

turned on and off with the ALARM LATCH ENABLE button. 

c) SET TRACKING ALARMS: allows an alarm to be set with respect to the set temperature.  It will move accordingly 

with a change of the temperature setting.  This option can be used for a high alarm, low alarm, or both settings. 

d) NO ALARMS PICKED: no alarm condition will be monitored. 
e) The “Expansion Connector Wiring Diagram” shows how customer‐supplied LED’s can be installed to externally 

signal various alarm conditions as well. 

 

 

Associated with the ALARM TYPE configuration are the HIGH ALARM SETTING box, LOW ALARM SETTING box, and 
the ALARM DEADBAND box.  If an alarm type has been selected, enter the desired high and low temperature 
values that you want to have trigger an alarm condition.  The ALARM DEADBAND option sets the hysteresis of the 
alarm values from 0.1 degrees to 100 degrees. 

 
2.6.3 SENSOR FOR ALARM 

a) CONTROL SENSOR: if this is selected, the primary sensor is used for monitoring alarm conditions. 
b) INPUT 2 SENSOR: if this is selected, the secondary sensor is used for monitoring alarm conditions. This requires 

that a secondary thermistor be installed, and a potentiometer or voltage/current levels cannot be used for 
adjusting the set point temperature. 

ALARM INDICATOR

ACTIVE ALARMS

ALARM INDICATOR

ACTIVE ALARMS

Advertising