23. CONTROL DEADBAND SETTING 

Write Command: 25 
Read Command:  59 
Interpret: 

Temperature or count span Input1 must move to toggle control output. When writing, 
first multiply the desired setting by 100

10

 and convert to hexadecimal for the “send 

value.” When reading, convert the “return value” to decimal and divide by 100

10

 to 

covert to °F/°C. 

          

24. INPUT1 OFFSET  

Write Command: 26 
Read Command:  5a 
Interpret: 

Value to offset Input1 by in order to calibrate external sensor if desired. When writing, 
first multiply the desired setting by 100

10

 and convert to hexadecimal for the “send 

value.” When reading, convert the “return value” to decimal and divide by 100

10

 to 

covert to °F/°C. 

 

25. INPUT2 OFFSET  

Write Command: 27 
Read Command:  5b 
Interpret: 

Value to offset Input2 by in order to calibrate external sensor if desired. When writing, 
first multiply the desired setting by 100

10

 and convert to hexadecimal for the “send 

value.” When reading, convert the “return value” to decimal and divide by 100

10

 to 

covert to °F/°C. 

 

26. HEAT MULTIPLIER 

Write Command: 0c 
Read Command:  5c 
Interpret: 

This multiplies the heater percentage of power to offset its effectiveness. When 
writing, first multiply the desired setting by 100

10

 and convert to hexadecimal for the 

“send value.” When reading, convert the “return value” to decimal and divide by 100

10

 

to interpret. 

 

27. COOL MULTIPLIER 

Write Command: 0d 
Read Command:  5d 
Interpret: 

This multiplies the cooling percentage of power to offset its effectiveness. When 
writing, first multiply the desired setting by 100

10

 and convert to hexadecimal for the 

“send value.” When reading, convert the “return value” to decimal and divide by 100

10

 

to interpret. 

 
 

28. OVER CURRENT COUNT COMPARE VALUE 

Write Command:  0e 
Read Command:  5e 
Interpret: 

This is the count compare value which determines an over‐current condition. Current 
is approximately 2.5 per count. Only integer values are allowed. Remember to convert 
to hexadecimal before sending.  

 
 