Improper tuning of this temperature controller can lead to excessive thermal cycling and/or overheating 
of the thermoelectric device, either of which are known to reduce the lifetime of any thermoelectric 
device.  Care should be taken to prevent the temperature of the TE device from going beyond the range 
specified by the device manufacturer.  Care should also be taken so that any thermal cycling of the TE 
device is a result of changes in the controller’s set‐point temperature and not instability at a given set 
point due to improper selection of the tuning variables. 

 
3.1

Connect ONLY the TE device to the controller (fans should not be connected to the controller): 

 

 

Positive TE device terminal to WP2 

 

 

Negative TE device terminal to WP1 

 

TE Technology’s standard thermoelectric cooling assemblies (TCA) have at least one fan on the heat sink. 
The standard configuration has the thermoelectric modules and fan(s) wired to a terminal block with 
jumpers across the terminals so that the fans and modules are connected in parallel. However, this 
configuration is applicable only when applying power directly from the power supply. When using the TCA 
with the temperature controller, the jumpers 

MUST

 be removed so that the controller is controlling 

power only to the thermoelectric modules. There must be no electrical connection between the fans and 
the modules; fans must be connected directly to the power supply, not to the controller. The controller 
will be damaged if this is not followed
. See the cooler manual for further details, but the picture below 
shows the basic setup. 

 

NOTE:  Generally there is approximately a 0.5 to 1.3 V drop from the power supply to the TE device.  You might 
need to adjust the power supply accordingly to ensure full power is delivered to the TE device when needed. 

 

Next, click the ON/OFF button in the OUTPUT section to turn on output power (again, make sure the set point 
temperature is appropriate for the TE device before applying output power).  The controller will begin to send 
output power to the TE device. 

 

Temperature Controller Connection

PROTECTION

DEVICES

DC POWER SUPPLY

THERMOELECTRIC

(PELTIER)

HOT-SIDE FAN

(ALL UNITS)

COLD-SIDE FAN

(AC-XXX UNITS ONLY)

TCA

TEMPERATURE

CONTROLLER

Terminal Block

Cover removed

for clarity. Re-

install before

operation.

Review electrical jumper connections. Remove electrical jumpers as required.