9. SENSOR TYPE 

Write Command: 2a  
Read Command:  43 
Interpret: 

0: TS141 5K 
1: TS67 OR TS136 15K 
2: TS91 10K 
3: TS165 230K 
4: TS104 50K 
5: YSI H TP53 10K 

 

10. CONTROL TYPE 

Write Command: 2b  
Read Command:  44  
Interpret:  

0 is deadband control. 
1 is PID control. 
2 is computer control. 
 

         11. CONTROL OUTPUT POLARITY 

Write Command: 2c  
Read Command:  45  
Interpret: 

0 is HEAT WP1+ and WP2‐. 
1 is HEAT WP2+ and WP1‐. 

          

12. POWER ON/OFF 

Write Command: 2d  
Read Command:  46  
Interpret:  

0 is off. 
1 is on. 

 

13. OUTPUT SHUTDOWN IF ALARM 

Write Command: 2e  
Read Command:  47  
Interpret: 

0 is no shutdown upon alarm. 
1 is to shutdown main output drive upon alarm. 

 

14. FIXED DESIRED CONTROL SETTING 

Write Command: 1c  
Read Command:  50  
Interpret: 

When writing, multiply the desired control temperature by 100

10

 and convert to 

hexadecimal.  This becomes the “send value.” When reading, convert the “return 
value” to decimal and divide by 100

10

 to convert to °F/°C. 

 

When CONTROL TYPE is set to “computer control”, the output power sent to the 
cooler can be set anywhere from ‐511

10

 to  +511

10

, corresponding to ‐100% to +100% 

output power. Remember to convert to hexadecimal before sending. 

 

15. PROPORTIONAL BANDWIDTH 

Write Command: 1d  
Read Command:  51  
Interpret: 

Fixed‐point temperature bandwidth distributed around the control setting in °F/°C.  A 
value of 5 °F/°C for bandwidth and control setting of 25 °F/°C would place the 
proportional band from 20 °F/°C to 30 °F/°C; that is, 5 ° above and 5 ° below set point. 

 

When writing, first multiply the desired bandwidth setting by 100

10

 and convert to 

hexadecimal for the “send value.” When reading, convert the “return value” to 
decimal and divide by 100

10

 to covert to °F/°C. 