Supply & return sensor wiring, Component & system wiring 21 – WattMaster VAV User Manual

Page 21

Advertising
background image

Component & System Wiring

21

Notes:

1.)All Wiring To Be In Accordance With

Local And National Electrical Codes
and Specifications.

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

WMVAV Controller Wiring

JOB NAME

03/24/04

VAV-SupRetTempWire1.CDR

Supply & Return Air Temperature Sensor To

1

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

Mount In HVAC

Unit Supply

Air Duct

Mount In HVAC

Unit Return

Air Duct

Supply

Air Temperature

Sensor

Return

Air Temperature

Sensor

WMVAV Controller Board

Supply & Return Sensor Information

The Supply and Return Air Temperature Sensors must be wired as shown in the
illustration below for proper operation. The Supply and Return Air Temperature
Sensors are 10K Type III thermistor sensors. The Supply Air Temperature Sensor
should be mounted in the unit discharge plenum or in the supply air duct. The Return
Air Temperature Sensor should be mounted in the return air duct. If the system has a
bypass damper installed, be sure the return air sensor is located upstream of the
bypass duct connection.

Supply & Return Sensor Wiring