Component & System Wiring

44

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

Connection Diagram

JOB NAME

02/11/04

G-ModServiceTool1A.CDR

OE391 Modular Service Tool

1 of 1

Typical Controller Board

Connector Cable

Modular Service Tool

Female DIN Connector

T

Block Base

erminal

(Remove Terminal Block)

PL101904 Adapter Board

Optional Connection For
Controllers Without DIN Connector

Male DIN Connector

Mode

Selection

ENTER

CLEAR

ESC

PREV

NEXT

DOWN

UP

6

5

4

DEC

7

0

8

1

3

2

9

MINUS

-

STATUS

SETPOINTS

SCHEDULES

CONFIGURATION

ALARMS

ON

OVERRIDES

BALANCE - TEST

Be Sure The Modular Service
Tool Is Connected To The
Supplied Power Pack Or Has
Fresh Batteries Installed Before
Attempting Programming Of The
Controller. Be Sure The Power Is
Turned Off On The Modular
Service Tool Before Connecting
The Cable To The Controller.

The Modular Service Tool Can Be Connected To Most
Controllers By Plugging One End Of The Supplied
Cable Into the Modular Service Tool DIN Connector
And The Other End Into The DIN Connector On The
Controllers.

Some Controllers Without DIN Connectors Require
Use Of The Supplied PL101904 Adapter Board Shown
Above. To Connect With Adapter Board, First Unplug
COMM Terminal Block From Controller Board. Plug
PL101904 Adapter Board Terminal End Into Terminal
Block Base On Controller. Plug DIN Connector Cable
Into DIN Connector On PL101904 Adapter Board . See
Optional Connection For Controllers Without DIN
Connector Above For Illustration Of This Connection.

Power On Button

T
SHLD
R

COMM

Modular Service Tool Connections