background image

Component & System Wiring

22

Notes:

1.)All Wiring To Be In Accordance With

Local And National Electrical Codes
and Specifications.

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

WMVAV Controller Wiring

JOB NAME

05/12/04

VAV-OATempWire1.CDR

Outside Air Temperature Sensor To

1

Outside AirTemperature Sensor

The Outside Air Sensor must be wired as shown in the illustration above for proper
operation. The Outside Air Temperature Sensor is a 10K Type III thermistor sensor.
The sensor should be mounted in the upright position as shown, in an area that is
protected from the elements and direct sunlight. Be sure to make the wiring splices
inside of the Outside Air Temperature Sensor weathertight enclosure.

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

Outdoor

Air Temperature

Sensor

WMVAV Controller

Make Splice Connections
Inside Sensor Enclosure
As Shown.

Caution:

Be sure to mount the Outside Air Sensor in an area that is not exposed to direct sunlight. A

shaded area under the eve of the building or under the HVAC unit rainhood is normally a good

location. If sensor is not located as specified, erroneous outside air temperature readings will

result. Unused conduit opening(s) must have closure plugs installed and must be coated with a

sealing compound to provide raintight seal. Water can damage sensor!

Outside Air Sensor Wiring