Component & system wiring 30, Vav/cav unit controller board – WattMaster VAV User Manual

Page 30

Advertising
background image

Component & System Wiring

30

Notes:

1.)All Wiring To Be In Accordance With

Local And National Electrical Codes
and Specifications.

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

Component Wiring Diagram

JOB NAME

OE354 - 4 Analog Input 1 Analog Output Expansion Board

2 of 3

Input #11 - Carbon Dioxide Sensor - Wiring

Input #10 - Remote Occupied Contact - Wiring

JO3

JO3

JO4

JO4

JO2

JO2

JO1

JO1

CX2

CX2

R10

R10

AOUT1

AOUT1

AIN4

AIN4

TB1

TB1

GND

GND

AIN2

AIN2

AIN3

AIN3

AIN1

AIN1

PU4

PU4

U2

U2

D5

D5

Q1

Q1

R8

R8

R9

R9

LM358

LM358

C5

C5

C1

C1

R7

R7

R6

R6

R5

R5

PU3

PU3

C4

C4

C3

C3

C2

C2

PU2

PU2

PU1

PU1

4 ANALOG IN MOD. I/O BD.

4 ANALOG IN MOD. I/O BD.

R3

R3

PCF8591P

PCF8591P

YS101784

YS101784

D4

D4

R4

R4

D3

D3

D1

D1

D2

D2

R2

R2

R1

R1

CX1

CX1

U1

U1

P1

P1

Normally Open
Dry Contact
(By Others)

Input #10 - Remote Occupied Contact

Jumper Must Be Off For AIN2

Pullup Resistor PU2 Must Be
Installed

Pullup Resistor PU3 Must Be
Removed As Shown

CO Sensor
(0-10VDC Signal)

2

1.

-

N

ot

Used

2.

-

N

ot

Used

4.

Relay

Common

5.

Relay

Norm

Closed

6.

4-20mA

Output

3.

Relay

Norm

Open

7.
Signal

Ground

8.

0-10V

Output

Pin

Designations

Pin

Designations

1.

AC+/DC+

2.

AC/GND

24V

AC

Line Voltage

GND

Warning

:

24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

Jumper J03 Must Be On
As Shown For CO Sensor
With 0-10VDC Signal
If

Be Removed

2

CO Sensor With 0-5VDC

Signal Is Used It Must

2

VAV/CAV Unit Controller Board

24VAC

GND

03/24/04

VAV-OE354-4ANALOGIN1OUT.CDR

4 Analog Input 1 Analog Output Expansion Board Wiring (Cont’d)