Supply fan vfd wiring, Component & system wiring 25 – WattMaster VAV User Manual

Page 25

Advertising
background image

Component & System Wiring

25

Notes:

1.)All Wiring To Be In Accordance With

Local And National Electrical Codes
and Specifications.

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

WMVAV Controller Wiring

JOB NAME

03/24/04

VAV-SupplyVFDWR1.CDR

Supply Fan VFD To

1

+

Supply Fan

Variable Frequency Drive

(By Others)

_

VFD 0-10VDC Input

GND

The VFD Unit Must Be Configured For 0-10VDC Input. The
Input Resistance At The VFD Must Not Be Less Than 1000
Ohms When Measured At The VFD Terminals With All
Input Wires Removed.

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

WMVAV Unit Controller Board

Caution:
Variable Frequency Drive Units Can Cause Large
Transient Noise Spikes Which Can Cause
Interference To Be Propagated On Other
Electronic Equipment. Use Shielded Wire
Wherever Possible And Route All
Sensor/controller Wiring Away From The Variable
Frequency Drive And The Air Handling Unit
Electrical Wiring.

Supply Fan VFD Wiring

Advertising