Lighting panel wiring for ge, Latching relay lighting contactors, Component & system wiring 51 – WattMaster VAV User Manual

Page 51: Relay expansion board, Lighting panel controller

Advertising
background image

Component & System Wiring

51

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

Using GE Latching Relays

JOB NAME

05/12/04

W-LightingPnl-GE1.CDR

OE310 Lighting Panel Controller Wiring

1

Note:
Set-up, Programming
And Monitoring Of
The Lighting Panel
Controller Requires
The Use Of A
Personal Computer
And PrismSoftware.

1.)24 VAC Must Be Connected So

That All Ground Wires Remain
Common.

3.)All Communication Wiring To Be 18

Ga. Minimum, 2 Conductor Twisted
Pair With Shield. Belden #82760 Or
Equivalent.

4.)It Is Recommended That All

Controllers Address Switches Are
Set Before Installation.

2.)All Wiring To Be In Accordance With

Local And National Electrical Codes
and Specifications.

Local Loop RS-485

Communications To Other

Controllers On The Local

Loop

Ribbon Connector

Relay Expansion Board

Ground

24V

All switches
(1 thru 4)
must be in the
“ON” position

EPROM

RAM

PAL

PIN 1

PIN 1

PIN 1

PIN 1

CPU

+V
+V

1

3
4
5
6
7
8

G
G

2

ANALOG

INPUTS

GND

SIG

+5V

ANALOG

OUTPUTS

A1

A2

G

T

SH

R

GND

24VAC

Lighting Panel Controller

Light Circuit 1

Light Circuit 2

Light Circuit 1

Light Circuit 2

Light Circuit 3

Light Circuit 3

Light Circuit 4

Light Circuit 4

Light Circuit 5

Light Circuit 5

Light Circuit 6

Light Circuit 6

Light Circuit 7

Light Circuit 7

T

SH

R

ON

OFF

24VAC

GE Lighting Relay- Circuit #1

(By Others)

Typical Wiring Shown For Circuit #1
All Other Circuits Are To Be Wired
Identically. Up to 7 Lighting Circuits May
Be Wired To Each Lighting Panel Controller.

K1

R1

R2

R3

R4

R5

R6

R7

R8

K2

K3

K4

K5

K6

K7

Light Sensor

(Optional)

See Note 1

Line Voltage

Line Voltage

16

8

4

2

1

Address Switch Shown Is

Set For Address 1

Address Switch Shown Is

Set For Address 13

Controller
Address Switch

This Switch Must Be
In The ON Position
As Shown

These Switches Should Be
In The OFF Position
As Shown

ADD

ADD

ADD

The Address For Each Controller

Must Be Unique To The Other Controllers

On The Local Loop

Required VA For Transformer

Each Controller = 10 VA Min..

Momentary Pushbuttons

(Optional)

Override Circuit #1

Override Circuit #2

Override Circuit #5

Override Circuit #3

Override Circuit #6

Override Circuit #4

Override Circuit #7

Caution:

If Lighting Contactor Coil Current Draw Is More Than 2

Amps And/Or Does Not Use A 24VAC Coil, A Pilot Duty Relay
That Has A Current Draw Of Less Than 2 Amps @ 24VAC Must
Be Used To Energize The Lighting Contactor. A Separate
Transformer Rated For The Total Lighting Contactor(s) Or Pilot
Relay Current Draw Must Always Be Used To Power The Circuit.

Note:

All Circuit Board
Contacts Are N.O.
All Contacts Are
Rated For 2 Amps
@ 24VAC Pilot
Duty Only
Do Not Apply Any
Voltage Greater
Than 24VAC

!

!

!

Caution!
Controller Must Have Address Switch Set Between 1 And 60

C

O

N

T

R

O

L

S

Lighting Panel Wiring For GE

®

Latching Relay Lighting Contactors