5 Installation Procedure

18

YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual

Communication Cable Wiring

Procedure

Follow the instructions below to connect the communications cable to the terminal block.

NOTICE: Tighten all terminal screws according to the specified tightening torque. Failure to comply can

cause a short-circuit or drive malfunction.

1.

Connect the communications cable to the terminal block as shown in the diagram
below.

Note: Communication lines should be separated from main circuit wiring and other electrical lines.

(Tightening torque: 0.22 to 0.25 (Nxm))

Figure 6

Figure 6 Comm Cable Wiring

2.

Take particular precautions to ensure that each cable is properly connected, and
that wire covering has not been accidentally inserted into the terminals.

3.

After the terminal block is fully attached to the CC-Link option, tighten the screws on
the left and right sides of the terminal block. (Tightening torque: 0.22 to 0.25 (Nxm))

Figure 7

Figure 7 Terminal Block Installation

DA DB DG SLD SLD

Terminal block

Preparing wire ends:

Screwdriver blade size

When not using
terminal extensions

about 5.5 mm

Pull back the sheilding and lightly
twist the end with fingers, keeping
the ends from fraying

CC-Link comm cable

(do not soldered ends)

Loosen the screws and
insert the cable into the
opening on the terminal block

Blade depth of
0.4 mm or less

Blade width of
2.5 mm or less

screwdriver blade size

Blade depth of
0.6 mm or less

Blade width of
3.5 mm or less

Advertising