9 troubleshooting – Yaskawa 1000 Series Drive Option - CC-Link Installation User Manual

Page 34

Advertising
background image

9 Troubleshooting

34

YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual

Table 13 LED Fault Display for CC-Link Option with Multiple Drives

{: On / †: Flashing /

×: Off / ∗: Either on or off

LED Status

Cause

Corrective Action

Master

Remote Device Addresses

(CC-Link Option)

Station 1 Station 2 Station 3

TIME {
LINE {
or
TIME

×

LINE {

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

Normal operation

L.RUN

×

SD

×

RD

×

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

The CC-Link Option for the first station is
not properly installed.

⇒Make sure the CC-
Link Option and drive
are connected together
properly.

L.RUN

SD

RD

L.ERR

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

The CC-Link Option for the first station is
damaged (most often all LEDs are out).

Note: Sometimes and error

will appear on the

drive’s operator

⇒Replace the CC-Link
Option.

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN

×

SD

RD

L.ERR

×

L.RUN

×

SD

RD

L.ERR

×

Because L.RUN after Station 2 is off,
either the comm. line between Station 1
and Station 2 is disconnected, or the
terminal block has come loose.

Make sure components
are connected correctly,
using the LEDs as a
guide to indicate a
proper connection.

L.RUN

×

SD

RD

L.ERR

×

L.RUN

×

SD

RD

L.ERR

×

L.RUN

×

SD

RD

L.ERR

×

Comm cable has short-circuited

⇒Look for any short-
circuits along the
communication lines
and fix any problems.

L.RUN

×

SD

RD

L.ERR

L.RUN

×

SD

RD

L.ERR

L.RUN

×

SD

RD

L.ERR

Comm cable is not wire properly

⇒Check the wiring for
the CC-Link Option
terminal block and fix
and mistakes.

L.RUN

×

SD

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN

×

SD

RD

{

L.ERR

×

The CC-Link Options for Station 1 and
Station 3 have been assigned the same
address.

⇒Enter the correct
station address and
cycle power.

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN

×

SD

×

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

The CC-Link Option for Station 2 has a
different comm speed setting than the
master device.

⇒Set the correct
communication speed
and cycle power.