8 CC-Link Data Table

YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual

25

Note: 1. If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register.

Using RYE (Frequency Reference 2 flag) too often can shorten the performance life of the drive's

internal memory.

2. Although RYE and RYF are triggered by the rising edge of the signal, they are otherwise enabled

depending on the value that is input.

When switching between monitors using RYC (Monitor Reference), RYC needs to be turned off and

then back on again after the monitor code has been changed.

RYE

Frequency
Reference 2

Sets the frequency in the remote register RW

W1

to

parameter d1-01 (Frequency Reference 1) and as the
drive’s main frequency reference at the same time.

Note: If the frequency reference is

set to be provided by the

operator

(i.e, b1-01 = 0), then switching

on RYE changes the frequency

reference.

All parameter settings are saved
when this flag is switched on.
Triggered by the rising edge of
the signal.

RYF

Command
Code Execute
Request

Request to execute the command code.

Triggered by the rising edge of
the signal.

RY10 to

13

Reserved

RY14

Terminal S1
Function

Multi-function input: H1-01

Function is disabled when for the
Forward Run Command (H1-01
= 40).

RY15

Terminal S2
Function

Multi-function input: H1-02

Function is disabled when for the
Reverse Run Command (H1-02 =
41).

RY16 to

19

Reserved

RY1A

Fault Reset

Resets a drive fault

RY1B to

1F

Reserved

Signal

Name

Description

Default