8 CC-Link Data Table

8

CC-Link Data Table

Remote I/O

The drive takes up a single station address in the buffer memory or the PLC. The table below

shows the drive I/O as seen from the PLC side.

Note: Refer to the PLC’s programming manual for information on the PLC’s buffer memory.

PLC

Drive

Table 6 Remote I/O Table (PLC

Drive)

Signal

Name

Description

Default

RY0

Forward Run

ON: Forward Run Command, OFF: Stop

RY1

Reverse Run

ON: Reverse Run Command, OFF: Stop

RY2

Terminal S3
Function

Multi-function input: H1-03

(H1-03 = 24: External Fault)

RY3

Terminal S4
Function

Multi-function input: H1-04

(H1-04 = 14: Fault Reset)

RY4

Terminal S5
Function

Multi-function input: H1-05

(H1-05 = 3: Multi-Step Speed 1)

RY5

Terminal S6
Function

Multi-function input: H1-06

(H1-06 = 4: Multi-Step Speed 2)

RY6

Terminal S7
Function

Multi-function input: H1-07

(H1-07 = 6: Jog Reference)

RY7

Terminal S8
Function

Multi-function input: H1-08

(H1-08=8, baseblock command)

RY8

Reserved

RY9

Drive Output
Interrupt

ON: Motor coasts to stop.
OFF: Drive will begin operating as soon as a Run
command is given.

RYA

External Fault ON: External Fault Input (EF0)

RYB

Motor
Revolutions /
Output
Frequency
Switch

Data contents for the remote register RW

R1

switches

between motor revolutions and output frequency.

Motor rotations are displayed
when not in V/f or OLV for PM.

RYC

Monitor
Reference

ON: Monitor data specified in the monitor code is set
to remote register RW

R0

.

RYD

Frequency
Reference 1

Frequency set to remote register RW

W1

becomes the

operating frequency for the drive.