8 CC-Link Data Table

YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual

27

Remote Register

PLC

Drive

Table 8 Remote Register (PLC

Drive)

Drive

PLC

Table 9 Remote Register (Drive

PLC)

Remote

Register

Name

Description

Request Flag

RW

W0

Monitor
Code

Sets the code number of the items to be displayed by the
monitor.

RYC (Monitor Execute
Request)

RW

W1

Frequency
Setting

Indicates which value is to be used to set the frequency.

• RYD (Frequency

Reference 1)

• RYE (Frequency

Reference 2)

RW

W2

Command
Code

Sets the command code to execute functions such as the fault
reset, fault history, parameter read, and so on.

RYF (Command Code
Execute Request)

RW

W3

Write Data

Sets the value to be used along with RW

W2

(Command Code)

as needed.

Remote

Register

Name

Description

Check Flag

RW

R0

Monitor
Data

Monitor data is stored according to RW

W0

(Monitor Code).

RXC (while monitoring)

RW

R1

Output
Frequency

Output frequency has been set without any errors. Set in the
units specified by o1-03 (Frequency Reference Setting Units).

RW

R2

Response
Code

Sets 00H when there are no problems with RW

W2

(Command

Code) and RW

W3

(Write Data).

Sets 01H through 03H if an error occurs.
Response Code:
00h: Normal
01h: Write-mode error (attempted to write during run, etc.)
02h: Command code error
03h: Data setting range error

RXF (Command Code
Execute Complete)

RW

R3

Read Data

Data is set according to the command code.