9 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual

31

Fault LED Display on CC-Link Option Side

Checking LED Operation

Table 11 LED Display

Note: If communication stops while the drive is running, check the following:

• Is the CC-Link properly installed?

• Is the CC-Link communication line connected to the CC-Link Option correctly? Is it loose?

• Is the PLC program working? Has the PLC CPU stopped?

• Did a momentary loss in power interrupt communications?

Faults that Occur with a Single Drive

The example below demonstrates how to read the LED display on the front cover of the

drive to determine the cause of a fault and corrective action.

Figure 10

Figure 10 Connecting a Single Drive

Table 12 LED Fault Display for CC-Link Option with a Single Drive

Communication circuitry is
damaged.

Perform a self-diagnostics check.

⇒ Replace the drive if the fault continues to occur.

YES

L.RUN

Switches on when data is being received normally. Turns off when the receive data is interrupted.

SD

Lights whenever the drive is sending data.

RD

Lights whenever the drive is receiving data.

L.ERR

Lights when a CRC or abort error occurs.

{: On / †: Flashing /

×: Off / ∗: Either on or off

L.RUN

SD

RD

L.ERR

Cause

Possible Solution

{

{

{

×

Normal communications

{

{

{

†

Error has occurred but
communication is normal

⇒Remove the source of noise interference.

Power
supply

CPU

Master

device

Station 1

DRIVE

CC-Link

Option

Advertising