9 troubleshooting – Yaskawa 1000 Series Drive Option - CC-Link Installation User Manual

Page 33

Advertising
background image

9 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual

33

Note: SD and RD may appear to flash with slower baud rates.

Faults when running multiple drives

The example below demonstrates how to read the LED display on the front cover of the

drive to determine the cause of a fault and the corrective action to take when multiple drives

are running from the same network. The example assumes that SW, M/S, and PRM on the

master device are all off, indicated that the master device is operating normally.

Figure 11

Figure 11 Connecting Multiple Drives on the Same Network

×

×

×

×

Data cannot be received
(CC-Link communications
cable may be disconnected)

⇒Check the wiring.

×

×

{

The station address or
communications speed is set
incorrectly

⇒Enter the proper settings and cycle power.

{

{

{

†

The station address or
communications speed was
changed without cycling
power afterwards.

⇒Return any incorrect settings to their original
values and cycle power.

⇒Enter the proper settings and cycle power.

{: On / †: Flashing /

×: Off / ∗: Either on or off

L.RUN

SD

RD

L.ERR

Cause

Possible Solution

Power
supply

CPU

Master

device

Station 1

DRIVE

Station 2

DRIVE

Station 3

DRIVE

CC-Link

Option

CC-Link

Option

CC-Link

Option

Advertising
This manual is related to the following products: