9 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual

29

Operator Display

Fault Name

EF0

External Fault Input from CC-Link Option
The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being
sent from the master
controller (PLC).

⇒ Remove the cause of the external fault.

⇒ Reset the external fault input from the PLC device.

Problem with the PLC
program

⇒ Check the program used by the PLC and make the appropriate corrections.

Operator Display

Fault Name

oFA00

CC-Link Option Fault (CN5-A)
CC-Link Option is not properly connected.

Cause

Possible Solution

Non-compatible option
connected to the drive

⇒ Connect an option that is compatible with the drive.

Operator Display

Fault Name

oFA01

CC-Link Option Fault (CN5-A)
CC-Link Option is not properly connected.

Cause

Possible Solution

Problem with the connectors
between the drive and CC-
Link Option

⇒ Turn the power off and check the connectors between the drive and CC-Link
Option.

Operator Display

Fault Name

to

oFA30 to

oFA43

CC-Link Option Fault (CN5-A)

Communication ID error

Cause

Possible Solution

CC-Link Option hardware
fault

⇒ Replace the CC-Link Option. Contact Yaskawa for assistance.

Operator Display

Fault Name

oFb00

CC-Link Option Fault (CN5-B)
Non-compatible option card is connected.

Cause

Possible Solution

Non-compatible option
connected to the drive.

⇒ Connect the correct option card to CN5-A.

Operator Display

Fault Name

oFb02

CC-Link Option Fault (CN5-B)
Two of the same option cards are connected at the same time.