Option led display, For det, 4 option components – Yaskawa SI-EP3 PROFINET Installation User Manual

Page 12

Advertising
background image

4 Option Components

12

YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

Option LED Display

The option has six LEDs:
Bi-color Status LEDs:

• Module status (MS) red/green

• Network status (NS) red/green

PROFINET LEDs:

• Network speed-10/100 yellow

• Link status and network activity-Link/Act green

The operational states of the option LEDs after the power-up diagnostic LED sequence is

completed are described in

Table 3

. The states with a number in parenthesis are the number

of pulses of 250 ms on, 250 ms off cycles, followed by 500 ms off, then repeating the cycle.

Wait at least 2 seconds for the power-up diagnostic process to complete before verifying

LED states.

Table 3 Option LED States

Name

Indication

Operating Status

Remarks

Color

Status

MS
(visible
through
drive cover)

OFF

Power supply OFF

Power is not being supplied to the
drive.

Green ON

Option

operating

The option is operating normally and
initialization is complete.

Green

Flashing (1)

Diagnostics

Diagnostic data available.

Green

Flashing (2)

Configuration tool

Identified by a configuration tool.

Red ON

Default MAC or fatal error
occurred.

Default MAC address has been
programmed or the option has
detected an unrecoverable error.

Red

Flashing (1)

Configuration error (non-fatal)

Configuration error.

Red

Flashing (2)

No IP (non-fatal)

No IP address assigned.

Red

Flashing (3)

No station name (non-fatal)

No station name assigned.

Red

Flashing (4)

Init failure (non-fatal)

Failed to initialize module.

Green/
Red

Flashing

Option self-test

The option is in self-test mode.