YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual

6 Option Related Drive Parameters

6

Option Related Drive Parameters

The following parameters are used to set up the drive for operation with the option.

Parameter setting instructions can be found in the drive product manual.
Confirm proper setting of the all parameters in

Table 6

before starting network

communications.

Table 6 Parameter Settings

No.

Name

Description

Default

b1-01

<1>

Frequency Reference
Selection

Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)

1

(Set to 3 for

PROFINET)

b1-02

<1>

Run Command
Selection

Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB

1

(Set to 3 for

PROFINET)

F6-01

Operation Selection
after Communications
Error

Determines drive response when a bUS error is detected
during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

4: Alarm (d1-04)

<2> <3>

5: Alarm Ramp to Stop

<2> <3>

1

F6-02

External Fault
Detection Conditions
(EF0)

Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation

0

F6-03

Stopping Method for
External Fault from
Communication Option
Board

Determines drive response for external fault input (EF0)
detection during communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

1

F6-07

NetRef/ComRef
Selection Function

0: Multi-step speed reference disabled
1: Multi-step speed reference allowed

1

F6-08

Reset Communication
Related Parameters

Determines if communication-related parameters F6-††
and F7-†† are set back to original default values when the
drive is initialized using parameter A1-03.
0: Do not reset F6-†† and F7-†† parameters
1: Reset F6-†† and F7-†† parameters
Note: Setting this parameter does not affect
communication-related parameters.

0